Addressable fire detection panel – 2 loops
– Produced to EN54-2, EN54-4 standards.
– 128-zone capacity.
– Automatic addressing capabilities.
– 220-240V AC power supply.
– Features 4 fully monitored siren outputs rated at 24 V/0.3 A and 1 programmable relay, plus 8 additional relays.
– Integrated power supply rated at 24 V/100 W and built-in battery charger for 24 V batteries up to 15 Ah capacity.
– The panels offer an extensive list of settings and features for controlling installed devices and sirens. These parameters can be easily adjusted using a PC-based program.
– Panel programming can also be carried out via an integrated USB port.
– Messages can be viewed on the LCD screen, while LEDs are used to display basic operations such as alarms, pre-alarms and faults.
– Operation is via the built-in 11-key keypad.
– There’s also a built-in security lock.
– Maximum siren delay is 10 minutes.
– Optional Ethernet control capability.
– Optional Modbus extension.
– Optional external printer extension.